Skip to content
Free Pipe Calculator

Pipe Pressure Drop Calculator

Free online calculator · No signup required

Calculate pipe friction loss from flow rate, inside diameter and length. Include fittings with a total K coefficient and compare pressure drop in kPa and psi, with head loss in metres and feet.

Use the actual inside diameter, not the nominal pipe size. Results update as you type.

Pipe dimensions
Fluid properties · water at 20°C by default

For hot water, glycol or another Newtonian liquid, enter density and viscosity at the operating temperature. Values stay in SI in both unit systems.

Pipe + fitting pressure loss

43.204 kPa

Total pressure loss
43.204 kPa / 6.266 psi
Straight pipe
43.204 kPa
Fittings (ΣK)
0 kPa
Friction per length
2,160.179 Pa/m
Head loss (fluid)
4.413 m / 14.48 ft
Velocity
2.037 m/s / 6.684 ft/s
Reynolds number
50,736
Darcy friction factor
0.02607
Flow regime
Turbulent

Includes straight pipe and your fitting K only. Add elevation, devices and required outlet pressure separately.

Free results and downloads. No email required.

See MEPFlow in action

Take the next step: automatic water pipe sizing.

Connect fixtures, hot and cold piping on your floor plan. MEPFlow calculates demand and pipe sizes using the selected regional method. Watch the domestic-water workflow below.

7 days free. Then $49 USD/month. Card required. Cancel anytime. Calculator inputs do not transfer automatically.

How to use the pressure drop calculator

  1. Enter flow, actual pipe inside diameter and straight length.
  2. Choose a roughness preset or enter manufacturer data. Add the sum of fitting K values for the same pipe diameter.
  3. For a liquid other than water at 20°C, open Fluid properties and enter density and dynamic viscosity at the operating temperature.

Pressure drop formula

Velocity: v = Q ÷ (πD²/4)

Reynolds number: Re = ρvD/μ

Straight-pipe pressure loss: Δp = f(L/D)(ρv²/2)

Fitting loss: Δp = ΣK × ρv²/2

Head loss: h = Δp/(ρg)

D is actual inside diameter. Q is volumetric flow. ρ is density in kg/m³, μ is dynamic viscosity in Pa·s, f is the Darcy friction factor and g = 9.80665 m/s².

Pressure loss through 20 m of pipe

Use 1 L/s, 25 mm inside diameter, 20 m length and 0.04572 mm roughness. With water density 998.2 kg/m³ and viscosity 1.002 mPa·s, velocity is 2.037 m/s and Reynolds number is about 50,736. The Darcy friction factor is 0.02607, giving 43.204 kPa of straight-pipe loss. Set ΣK to 3 to add 6.214 kPa of fitting loss.

Straight pipe: 43.204 kPa. With ΣK = 3: 49.418 kPa total, or 5.048 m of fluid head.

Try the example above

What the pressure-drop result includes

The total is the friction loss through the entered straight pipe plus the loss from your fitting coefficient. It is not the pressure available at a fixture or a complete pump selection.

For an open water-supply path, account for elevation, meters, backflow devices and the required terminal pressure. In a closed hydronic circuit, use the complete supply-and-return route and equipment losses. Avoid counting a fitting twice through both equivalent length and K.

Darcy-Weisbach and the friction factor

The calculation uses SI internally, then converts pressure to kPa or psi and head to metres or feet. Here f is the Darcy friction factor, which is four times the Fanning factor.

For Reynolds numbers below 2,300, f = 64/Re. At 4,000 and above, the Colebrook-White equation is solved iteratively. Between those limits, a linear interpolation between the boundary friction factors gives an explicitly flagged estimate. Transitional flow is uncertain; this interpolation is not the EPANET transition algorithm.

Why pipe diameter and material matter

A smaller bore increases velocity at the same flow. It also increases the length-to-diameter ratio, so pressure loss can change sharply when a pipe size changes. Compare actual inside diameters, not just nominal labels.

The new-pipe roughness presets follow the EPA EPANET manual. Age, deposits, joints and lining can change the effective roughness. Use project or manufacturer data when available.

Water, hot water and glycol

Water at 20°C is the starting example: density 998.2 kg/m³ and dynamic viscosity 1.002 mPa·s. Temperature and glycol concentration change both properties. Enter values for the actual operating condition before using the result.

This tool assumes steady flow of a single-phase Newtonian liquid in a full circular pipe. It does not model compressible gas, steam, two-phase flow, water hammer or a branched-network flow balance.

Frequently asked questions

How do I calculate pressure drop in a pipe?

Find velocity from flow and inside area, calculate Reynolds number and Darcy friction factor, then use Δp = f(L/D)ρv²/2. Add fitting losses and any separate device losses for the full path.

What is the difference between pressure drop and head loss?

Pressure drop is energy loss per unit volume; head loss is energy loss per unit weight. Divide pressure loss in pascals by density × 9.80665 to obtain metres of the flowing fluid.

Does doubling pipe length double pressure loss?

For the same bore, flow, roughness and fluid, straight-pipe loss doubles. Fitting loss stays the same if the fittings are unchanged.

Can I calculate pressure loss through elbows and valves?

Enter their total K coefficient. Use coefficients referenced to the velocity in the entered pipe diameter. Manufacturer pressure-loss curves may be more appropriate for control valves, backflow devices and equipment.

Is this a Hazen-Williams calculator?

No. It uses Darcy-Weisbach, with viscosity and density as explicit inputs. Hazen-Williams uses a different empirical C coefficient; do not enter that C value as absolute roughness.

Continue the calculation

Engineering reference

See the US EPA EPANET 2.2 manual: pipe head loss, roughness and minor losses. This calculator uses the equations described above; it is not the EPANET network solver.

Plumbing
Calculate water-supply fixture units and a preliminary pipe size using NPC 2020. Includes private/public fixtures, direct-flush valves and worked examples.
Plumbing
Add drainage fixtures, calculate NPC 2020 fixture units, and size sanitary branches, stacks, building drains and sewers by hydraulic load and slope.
Plumbing
Calculate water volume in one pipe or a whole pipe inventory, in litres, US gallons and Imperial gallons.
Plumbing
Free domestic hot water recirculation calculator. Convert piping heat loss and allowable temperature drop into required recirculation GPM and L/s.
Plumbing
Calculate water velocity from flow and inside diameter. Use L/s, L/min, m³/h, US GPM or Imperial GPM and check a target velocity.
Plumbing
Free water heater recovery calculator. Convert gallons per hour and water temperature rise into required input BTU/hr or calculate recovery GPH from heater capacity and efficiency.