Skip to content
Free Hydronics Calculator

Hydronic Pump Head Calculator

Free online calculator · No signup required

Add the pressure losses along the critical hydronic circuit and convert total pressure drop into pump head.

Total pressure drop

10 psi

Pump head

23.1 ft

Pressure drop

68.9 kPa

For a completely closed hydronic loop, do not add static building elevation to the circulator head. Final pump selection requires the design flow and manufacturer pump curve.

Your next design step

Review the circuit behind the pump duty.

Lay out connected piping and equipment in MEPFlow, then review the flow and pressure-loss assumptions for the circuit.

Keep this check: Check the complete supply-and-return route and equipment losses before selecting the pump.

7 days free. Then $49 USD/month. Card required. Cancel anytime. Create a project and choose your workflow. Calculator inputs do not transfer automatically.

How the Hydronic Pump Head Calculator Works

A closed hydronic system circulator is selected to overcome friction and component pressure losses around the operating circuit. Static building height is not added as pump head in a closed loop because the fluid rises and falls within the same circuit.

Enter the design-flow pressure drops for pipe and fittings, terminal or coil, boiler or heat exchanger, control valve and other components. The calculator sums the critical path and converts pressure drop to feet of fluid head using specific gravity.

Final pump selection must place the required design flow and head on the manufacturer's pump curve and check efficiency, NPSH where applicable, minimum flow, control strategy and available motor power.

Calculation basis

Head (ft) = Pressure Drop (psi) × 2.31 ÷ Specific Gravity

When to Use This Calculator

  • Boiler-loop pump selection
  • Chilled-water branch checks
  • Heat-pump hydronic circuits
  • Critical-circuit pressure summaries

Engineering Checks Before Final Design

  • Use pressure drop at actual design flow.
  • Do not add static elevation head for a completely closed loop.
  • Final selection must be checked on a pump curve.

Related Engineering Guides

Continue with the calculation methods, design checks and worked examples most closely related to this tool.

Frequently Asked Questions

Do I add building height to hydronic pump head?

Not in a completely closed loop. The circulator primarily overcomes friction and component resistance because elevation gained on one side is recovered on the other.

How many feet of head is 1 psi?

For water near standard conditions, approximately 2.31 ft of head per psi. The calculator corrects this by specific gravity.

Which circuit should I calculate?

Use the circuit that produces the highest required pump head at the relevant design flow, commonly called the critical circuit.

Does this select a pump model?

No. It provides the design duty point; use the manufacturer's pump curves for model selection.

Hydronics
Free BTU to GPM hydronic calculator. Convert heating or cooling load and water delta-T into GPM, L/s and kW using the common Q = 500 × GPM × ΔT relationship.
Hydronics
Free hydronic buffer tank sizing calculator. Estimate gallons and litres from heat-source output, minimum concurrent load, desired run time and allowable water temperature swing.
Hydronics
Free hydronic expansion tank calculator for water systems. Estimate thermal expansion volume and minimum diaphragm tank volume from system volume, temperatures and operating pressures.
HVAC
Calculate minimum breathing-zone outdoor airflow using occupancy, floor area and the selected space type.
HVAC
Calculate minimum exhaust airflow requirements for common commercial and institutional spaces.
HVAC
Size round and rectangular ductwork from any two of flow rate, friction rate, velocity or diameter using Colebrook-White and Darcy-Weisbach.