Skip to content
Duct Design

HRV and ERV Sizing in Canada: Airflow, Static Pressure and Winter Operation

An HRV labelled 150 CFM may not deliver 150 CFM through your installed ductwork. Check the required airflow, both pressure paths and the winter operating sequence together.

Published by MEPFlow · Methods and limitations · Primary references

September 10, 2026 7 min read Updated September 10, 2026

Use the method while you read

Follow the worked examples, check your inputs and use the related MEPFlow tool to explore your own design.

Open the free static-pressure calculator
In this guide: jump to a step

Selecting a heat-recovery or energy-recovery ventilator requires more than matching a catalogue airflow to a room count. Establish the required outdoor airflow, calculate the resistance of both airstreams and check the unit's performance at those conditions. Then confirm that the winter sequence and distribution arrangement still meet the design intent.

This guide explains the selection workflow for Canadian projects without assigning one ventilation rate to every house or building. Residential and commercial ventilation can use different requirements. The applicable building code, referenced standards and project criteria determine the starting airflow.

Use this check alongside MEPFlow’s HVAC and ventilation design workflow to connect ventilation assumptions to the room and duct layout. Confirm the HRV/ERV operating point with the manufacturer.

1. Choose the correct ventilation requirement

Identify the building use and the required ventilation method before opening a calculator. For a commercial occupied zone, an ASHRAE 62.1 breathing-zone calculation may be one part of the design. It is not automatically a Canadian whole-house HRV sizing method, and it is not the final intake calculation for every multiple-zone system.

Record the continuous design duty, any boost duty, local exhaust provisions and the control strategy. A higher temporary speed may serve a different purpose from the normal ventilation setting. Define which condition governs the equipment and which conditions the duct system must accommodate.

  1. 1.List the served spaces

    Identify where fresh air is delivered, where stale air is collected and how air travels between them.

  2. 2.Record the basis of airflow

    Keep the source, edition and calculation with the schedule. A generic ACH target without a source is not a design requirement.

  3. 3.Check simultaneous exhaust

    Kitchen hoods, dryers and other exhaust systems may affect building pressure independently of the HRV or ERV.

2. Understand what the recovery core changes

An HRV transfers sensible heat between airstreams; an ERV also transfers some moisture. Neither name proves that a product maintains a particular indoor humidity or eliminates the need for heating and cooling equipment. The result depends on outdoor conditions, indoor moisture sources, airflow and the selected core.

Choose from rated performance and the moisture-control objective. A cold Canadian climate does not make one core type universally correct for every building. High indoor moisture production, summer humidity and the winter frost strategy can influence the choice.

Two separate airstreams pass through a heat-recovery core: outdoor air becomes supply air, while indoor extract air is discharged outdoors. Heat transfers through the core; the diagram does not represent recirculation.Outdoor intakeSupply to roomsExhaust outsideExtract from roomsRecovery coreHeat transferSeparate air pathsCheck both airflow / pressure duties and winter operation
Two separate airstreams pass through a heat-recovery core: outdoor air becomes supply air, while indoor extract air is discharged outdoors. Heat transfers through the core; the diagram does not represent recirculation.

Heat recovery is not a reduction in required fresh-air delivery

The core reduces part of the conditioning load. It does not justify lowering the required outdoor-airflow rate unless the governing design procedure specifically permits that change.

Take the next step on your own floor plan

Create a MEPFlow account to work through loads, ductwork, domestic water or hydronic layouts in your browser.

Start 30-Day Free Trial

3. Calculate supply and exhaust resistance separately

Trace the outdoor intake-to-supply path and the room-extract-to-discharge path. Add losses for the duct, fittings and components on each relevant route. Compare the resulting operating points with the unit's published performance definition, taking care not to double-count internal filters or core losses already included in the rating.

The two airstreams do not necessarily have equal resistance. One may have a longer exterior duct, different grilles or a more restrictive fitting arrangement. Balanced airflow therefore cannot be assumed from identical speed settings alone.

Hypothetical pressure budget at 150 CFM per airstream
External itemSupply pathExhaust path
Straight duct25 Pa20 Pa
Fittings35 Pa30 Pa
Grilles and exterior terminals40 Pa30 Pa
External total100 Pa80 Pa

Check the manufacturer's pressure definition

This example assumes the listed components are external to the rated unit. Use the actual catalogue definition and curves when comparing 150 CFM at 100 Pa supply and 80 Pa exhaust resistance.

4. Estimate the winter sensible load transparently

Consider an illustrative balanced flow of 150 CFM, approximately 70.8 L/s, with outdoor air at −20°C and indoor air at 21°C. Using a constant volumetric heat capacity of 1.2 kJ/(m³·K), the untreated sensible ventilation load is approximately 3.48 kW.

For a simple teaching calculation, an assumed sensible temperature effectiveness of 70% would leave about 30% of that load, or 1.05 kW. This is not an annual energy calculation, a frost-cycle model or a substitute for certified net performance. Use actual air properties and the required method for the project.

Q ≈ 1.2 × 0.0708 × 41 = 3.48 kW

Illustrative residual at 70% sensible effectiveness: 3.48 × (1 − 0.70) ≈ 1.05 kW. This simplified relationship excludes fan heat, imbalance, leakage, latent effects and defrost.

5. Review frost control and installation

At low outdoor temperatures, core frost protection can change how the unit operates. Review whether the sequence uses preheat, recirculation, interrupted supply or another approach, and what happens to delivered outdoor air during that sequence. Do not assume a mild-weather efficiency number applies unchanged through a severe winter cycle.

Coordinate condensate collection where applicable, drain freeze protection, intake and exhaust placement, insulation and vapour control on cold ducts, access for filters, and service clearances. A good calculation can still produce poor performance if installation creates avoidable resistance or maintenance becomes impractical.

  • Use the actual performance data at the intended continuous and boost settings.
  • Confirm that the selected unit and ductwork remain serviceable after ceiling coordination.
  • Check air-transfer paths when room doors are closed.
  • Document interaction with the furnace or air handler where systems are connected.

6. Balance and verify after installation

Commission the system by measuring supply and exhaust delivery under the intended operating conditions. Record settings, airflow measurements and the filter condition. Set balancing devices using measured performance rather than assuming that installed duct lengths match the design perfectly.

For the design workflow, establish ventilation first, use the duct and pressure tools to check distribution, and then compare real HRV or ERV performance. MEPFlow can help with the calculation and layout stages; the final selection still requires manufacturer curves and a documented installation and commissioning plan.

  1. 1.Measure both airstreams

    Verify the required outdoor supply and exhaust rather than only total fan operation.

  2. 2.Check normal and boost operation

    Confirm controls, boost inputs and any integration with the main air handler.

  3. 3.Leave a maintainable record

    Give the operator the settings, filter requirements and maintenance instructions so performance can be retained.

Frequently asked questions

Can I size an HRV with the ASHRAE 62.1 calculator?

That calculator supports a breathing-zone calculation for applicable spaces. It does not establish every Canadian residential ventilation requirement or complete the zone and system procedure.

Does 150 CFM on the label guarantee 150 CFM installed?

No. Delivered airflow depends on the operating setting and the connected resistance. Compare the actual duty with the manufacturer's performance data and verify during commissioning.

Does an ERV replace a dehumidifier?

Not automatically. Moisture transfer can reduce part of a ventilation load, but indoor moisture control depends on the building, climate and equipment. Check the latent load and control requirements separately.

Continue the engineering workflow

Put this guide into practice with MEPFlow

Move from the calculation method into a connected browser-based design workflow while keeping the assumptions visible for engineering review.

Start 30-Day Free Trial

Primary references

Use the edition and method accepted for your project. These authoritative resources provide further context; this article is educational and is not a code-compliance determination.