How to Size Domestic Water Pipes in Canada: NPC 2020 Step by Step

Use NPC 2020 water-supply fixture units to organize cold- and hot-water demand, developed length, pressure checks and pipe selection.

Published by MEPFlow · Methods and limitations · Primary references

August 31, 2026 9 min read Updated September 10, 2026

Use the method while you read

Follow the worked examples, check your inputs and use the related MEPFlow tool to explore your own design.

Open the free domestic water pipe calculator
In this guide: jump to a step

Canadian domestic water pipe sizing is not a simple sum of every fixture's full-flow rate. The National Plumbing Code of Canada (NPC) 2020 uses water-supply fixture units to represent intermittent demand from plumbing fixtures. Those fixture units support service, hot-water and cold-water pipe sizing, but the result must still be checked against available pressure, elevation, developed length, material, velocity and the requirements adopted in the project jurisdiction.

Water-supply fixture units are also called WSFU in many searches and design references. They are not the same as drainage fixture units used to size sanitary piping. When each water-supplied fixture is assigned the applicable NPC value and use category, a connected network can accumulate downstream hot and cold fixture-unit loads automatically.

Apply the fixture and sizing workflow in MEPFlow’s plumbing and domestic-water design software, where connected fixtures and cold/hot pipe layouts can be reviewed with the selected sizes.

For repeated network calculations, the plumbing design software comparison explains how to evaluate demand, pressure and the model together.

Quick example: a pipe-size candidate is only the first check

An original schedule of two low-flush tank toilets, two low-flow lavatories and a domestic low-flow sink gives a combined 7.2 water-supply FU using the stated private-use NPC 2020 entries. At the 5 ft/s Table F column, NPS ⅝ carries 6.5 FU and NPS ¾ carries 9 FU. The first table candidate is therefore NPS ¾. Reproduce it with the free calculator's worked-example button.

Now ask whether the remote fixture has sufficient pressure. The Table F lookup does not know the entry pressure, elevation, pipe material, actual route or component losses. Keep that gap visible instead of labelling the table candidate a completed plumbing design.

A domestic water main serves two washrooms and one sink. Loads accumulate toward the service; a separate hot-water branch originates at the heater.WaterheaterService → accumulating connected loadWashroom AWashroom BSinkHot-water distributionCold-water main
A domestic water main serves two washrooms and one sink. Loads accumulate toward the service; a separate hot-water branch originates at the heater.

Use the correct combined fixture load

The combined FU column is not necessarily cold FU plus hot FU. Direct-flush valves also use a cumulative sequence, not the first-valve value multiplied by quantity.

What a water-supply fixture unit represents

A water-supply fixture unit is a relative demand value, not a flow rate. It represents the load a fixture places on the water-distribution system while accounting for characteristics such as discharge rate, duration and frequency of use. The conversion from fixture units to probable flow is nonlinear because the chance that many fixtures operate simultaneously changes with the size and type of the connected group.

Fixture-unit values and demand conversions must come from the plumbing code, standard or approved design method applicable to the project. Private and public use can have different values. A software catalog can reduce data-entry work, but the designer remains responsible for confirming that its source and edition match the jurisdiction.

Code editions matter

NPC 2020 is a national model code, not an edition automatically in force everywhere. NPC 2025 has also been published. Confirm the edition adopted by the province or territory, local amendments and authority requirements before issuing a design.

Take the next step on your own floor plan

Create a MEPFlow account to work through loads, ductwork, domestic water or hydronic layouts in your browser.

Start free trial

NPC 2020 fixture-unit tables used for water pipe sizing

In NPC 2020 Division B, Article 2.6.3.2 assigns hydraulic loads to water-supplied fixtures. Tables 2.6.3.2.-A through 2.6.3.2.-D cover the fixture-unit inputs and related categories used by the sizing procedures. Start by selecting the correct fixture description and use condition; do not substitute drainage fixture units from Part 2.4.

Appendix Note A-2.6.3.1.(2) then outlines methods for sizing the water service, hot-water piping and cold-water piping. The small-building method uses developed length and available-pressure ranges, while Table A-2.6.3.1.(2)-F supports the average pressure-drop and velocity method. A fixture-unit total is therefore an input to pipe sizing—not a complete pipe size by itself.

NPC 2020 references for domestic water pipe sizing
NPC 2020 referenceWhat it is used forWhat the designer must confirm
Tables 2.6.3.2.-A to -DAssign water-supply fixture-unit loadsFixture description, public/private use and hot/cold application
Note A-2.6.3.1.(2)Procedure for service, hot-water and cold-water sizingWhich accepted method applies to the project
Table A-2.6.3.1.(2)-ASmall-building sizing by pressure range and developed lengthMinimum available pressure, elevation and component losses
Table A-2.6.3.1.(2)-FPipe size, flow, fixture-unit and velocity relationshipPipe material, permitted velocity and pressure-loss basis

Cold, hot and total fixture-unit paths

A fixture that uses both hot and cold water contributes to each side according to the selected method. A cold-only fixture contributes only to the cold-water network. The cold-water service must account for the cold demand delivered directly to fixtures and the water that ultimately feeds the hot-water system. The hot-water distribution is evaluated from the fixtures connected downstream of the heater or tank.

This is why topology matters. A branch serving one lavatory should not inherit the demand of an unrelated fixture on another branch. As pipes merge toward the source, their downstream fixture-unit totals increase. A connected drawing makes that accumulation traceable.

Network quantities to review
LocationPrimary quantityDesign check
Fixture branchFixture-specific demand and minimum branchLocal code minimum, material and connection size
Distribution branchDownstream cold or hot fixture unitsProbable flow, velocity and pressure loss
Hot-water outletConnected hot fixture unitsHeater connection, distribution demand and recirculation strategy
Building serviceCombined probable cold-water demandAvailable pressure, meter/backflow losses and peak demand

From fixture units to probable demand

The demand conversion is usually performed with a table or curve associated with the adopted method. It should not be replaced by a linear rule such as one gallon per minute per fixture unit. At small fixture counts, minimum branch and fixture-connection requirements can govern even when the probable-flow calculation appears low.

A good result page shows both the accumulated fixture units and the resulting probable flow. That lets the reviewer distinguish a data issue from a pipe-sizing issue. If a service demand looks unexpectedly small, the first check is whether fixture types and usage categories were assigned—not whether the final pipe-size table rounded incorrectly.

Pressure is the second half of pipe sizing

A pipe can satisfy a velocity rule and still fail to deliver adequate residual pressure at the remote fixture. Start with the minimum available pressure, then subtract static elevation, meter and backflow losses, equipment losses, valve and fitting losses, and pipe friction. The remaining pressure must satisfy the controlling fixture or device at design demand.

Available residual = source pressure − elevation loss − component loss − pipe and fitting loss

Use the project's design pressure basis and the adopted method for simultaneous demand. Pressure can also vary over time, so the minimum documented supply condition is more useful than a single favourable field reading.

  • Include elevation to the hydraulically remote fixture.
  • Account for meters, backflow preventers, pressure-reducing valves and treatment equipment.
  • Use actual developed length and fittings, not only the straight plan distance.
  • Check both low-pressure performance and any need for pressure control at high supply conditions.

A practical domestic-water sizing workflow

The workflow below keeps demand, geometry and pressure checks in the order they depend on one another. It also makes revisions easier when a fixture type or branch changes.

  1. 1.Build the connected network

    Place the service, hot-water source and fixtures, then connect cold and hot branches to their actual sources.

  2. 2.Assign fixture types and usage

    Use the source accepted for the project and distinguish public from private use where required.

  3. 3.Accumulate fixture units

    Calculate the cold and hot totals downstream of every pipe segment.

  4. 4.Convert to probable flow

    Apply the accepted demand table or curve, including any minimum branch rules.

  5. 5.Select preliminary sizes

    Apply material, velocity and sizing criteria to the calculated flow.

  6. 6.Verify the pressure path

    Calculate the controlling service-to-fixture route with elevation, components, fittings and developed length.

Common domestic-water sizing errors

Fixture-unit automation removes repetitive arithmetic, but it cannot decide whether the underlying fixture schedule, code basis and pressure data are correct. These checks remain important on every project.

  • Leaving fixtures unassigned, which causes them to contribute zero demand.
  • Using private-use values for a public or assembly occupancy without review.
  • Treating fixture units as if they were gallons per minute.
  • Sizing only for velocity and ignoring available pressure at the remote fixture.
  • Forgetting the hot-water system's contribution to building service demand.
  • Using plan length instead of developed length and omitting valves or fittings.
  • Assuming one national code edition is adopted unchanged in every Canadian jurisdiction.

Frequently asked questions

Are water-supply fixture units the same as drainage fixture units?

No. Water-supply fixture units represent probable demand on potable-water piping. Drainage fixture units represent hydraulic load on sanitary drainage piping. Use the tables for the system being designed.

Are fixture units the same as GPM?

No. Fixture units are relative demand values. They must be converted to probable flow using the table, curve or method accepted for the project.

Why do public and private fixtures have different values?

Public fixtures can have different frequency and simultaneity assumptions. The applicable code or approved method defines the values and categories.

Does the largest fixture-unit total always determine pipe size?

Demand is only one input. Minimum branch size, available pressure, elevation, developed length, components, velocity and material criteria can govern.

Can I use the same plumbing table everywhere in Canada?

Do not assume so. Confirm the code edition adopted by the province or territory, local amendments and the authority having jurisdiction.